Input Points
On this screen the details of all nodes that are input points are entered. Input points are the points in the network where the network is pressurised ie. connected to a water supply or pump. An input node cannot be connected to more than one pipe. If Calculate “Input Point Flow/Pressure” is not being used and a pump is installed drawing water from the mains or a storage tank, it is better to enter the pump as a booster pump.
The buttons on the Tool Bar for this page are:
Close - exits this screen
Deletes the current line (input point).
Help on the current tab page.
The input items for input points are:
Pressure 1 OR
Flow 1, Pressure 1, Flow 2, Pressure 2,....Flow n, Pressure n
Loss Coeff Tank Exit (FIXED Input only)
When linear, curve or Q185 is selected, once sufficient points are entered, a graph appears in the lower portion of the screen displaying the points and the fitted curve. This is a useful check on the entered values and in the case of "curve", whether the curve fit is reasonable. At the right end of the graph there is provision for extending the curve to check, in the case of curve, that the curve behaves acceptably past the last point on the graph.
If a piping network is entered and the pressure at the input point is such that there is insufficient pressure available to ensure a positive discharge through all sprinkler heads or nozzles, the calculation program may iterate to an impractical solution. The usual result, is that the program aborts with the error message:-
WARNING - DH/DQ NOT NEGATIVE - COMBINATION OF PUMP PARAMETERS PROBABLY INCORRECT.
The program can also sometimes end up with negative flows through the sprinklers. It is recommended therefore particularly when using Calculate “Input Point Flow/Pressure” (in which case the entered input pressure is a first estimate only) that the user enters a high value rather than a low value.
Multiple Input Points
When modeling systems with more than one input point, Calculate “Input Point Flow/Pressure” can be used and the program will then determine the flow and pressure at the nominated input point. The other input points must then have an actual characteristic curve or an actual fixed pressure defined. If Booster Pump Flow/Pressure is selected, all input points must have actual characteristics or an actual fixed pressure defined..