Operating Sprinklers Tab Page

On this Tab Page the Operating Sprinklers in the GRID are identified. Up to five rectilinear non overlapping sets of operating sprinklers can be entered. Also the program can be requested to determine the most remote region for the selected operating sprinklers. Both the operating sprinklers and the Remote area to be considered are identified by the row and column numbers of the bottom left hand corner and top right hand corner of a rectangle that contains the operating sprinklers or remote area.

The buttons on the tool bar at the top of the screen are:

imageebx_482209733.gif Close - exits this screen.

imageebx_463499438.gif Show Errors.

imageebx_5174786.gif Copies the GRID display to the clipboard (to be pasted into a report for example).

imageebx_780282784.gif Saves the GRID display as a Bit Map.

imageebx_-1174288340.gif Zooms the GRID display in and out.

imageebx_-402274554.gif Help on the current tab page.

imageebx_516318643.gif  View GRID.

The operating sprinklers and Remote region are entered on a form that floats over the graphic display.

The buttons on the floating form are:

imageebx_1194395346.gif Adds a set (line)of operating sprinklers to the table ready for inputting data.

imageebx_668880439.gif Deletes a set (line) of operating sprinklers from the table.

A pair of radio buttons to select whether operating sprinklers or the remote area is being entered.

Operating Sprinklers

The items of input for each set of operating sprinklers are:

Column number bottom left

Row number bottom left

Column number top right

Row number top right

Minimum flow of the operating sprinklers 

k factor of the operating sprinklers

Pressure Exponent

The operating sprinklers can be identified by windowing the sprinklers using the mouse. When this method is employed the row and column numbers are automatically inserted on successive lines in the floating form over the display.

As an alternative to picking the row and column numbers by windowing on the display, row and column numbers for the operating sprinklers can be entered manually on the floating form.

After the sprinklers that are operating have been identified the rest of the sprinkler details (minimum flow and k factor) must then be entered.

Remote

If it is required that the program determines the most remote (unfavourable) area of operation for the selected sprinklers, the area of the GRID to be considered for this is entered on the Remote line on the floating form, by either windowing the area required or alternatively manually entering the row and column numbers.

The program will then calculate the hydraulically most remote region for the nominated operating (discharging) sprinkler heads by moving the operating sprinklers around the GRID over the remote area specified.

The REMOTE calculation causes the set of operating sprinklers to move over all combinations of the specified remote region, with all operating sprinkler groups moving together as entered.

The most remote region is defined as the sprinkler locations that produces the least flow from any of the operating sprinklers.

When the calculations are performed the program prompts for the output file as normal but also a message form is displayed asking:

Do you want to save the existing data with REMOTE in it in a backup file?.

This is because after the program has calculated the REMOTE area the location of the operating sprinklers is moved to this area and saved in the current data file and also loaded into the program, i.e., with the new sprinkler locations and the REMOTE removed.

Note that REMOTE is only available when the program is run with GRID input, i.e. it will not work in a file that has been XPANded.