Pressure Exponent
Sprinklers and spray nozzles are designed to produce certain spray characteristics. It is generally accepted in the fire protection industry to use the discharge coefficient (or k factor) when determining the flow through a sprinkler or nozzle. i.e. Q = k x Pn where the pressure exponent n is taken as 0.5. Highly engineered sprays, as opposed to standard deflection type sprinklers, often contain complex internal and external geometries to form the distinctive spray patterns. In order to account for the different flow characteristic of these types of discharges, the pressure exponent can be considered as an input variable rather than a constant.
Typical Pressure exponents are:
Spray/Nozzle Type Pressure Exponent
Deflector type Sprinklers 0.50
Swirl Type Atomisers 0.50
Spiral Nozzle 0.50
Full Cone 0.47
Wide Angle Full Cone 0.44
If a value is not entered, the program assumes a default value of 0.50