Warning if Velocity Exceeds
The program prints warning messages for all pipes in which the velocity exceeds a given value. The program has preset values depending on the sprinkler code selected, but these can be overwritten by the user here
The required value is in m/sec for metric units, or in ft/sec for US or British Imperial units. The allowable ranges in the program are:
AS 2118Â 3 to 10 m/s
NFPA NSZ 4541 and SSCP52Â 3 to 15 m/s (10 to 50 ft/sec)
Although most Sprinkler Codes do not stipulate a maximum limit on velocities, some insurance companies do.
Note: In AS2118 Amendment 3, the VELOCITY IN VALVE SETS IS LIMITED TO 6 M/S. The program does not check for this.