Tips and FAQ
Moving Around the Screens
There are two types of screens used for data entry, those with a tabular spreadsheet type format e.g., the Pipes Screen, where each field is a cell in a table, and those with separate (boxed) fields e.g., the Project Screen.
To move from field to field (or cell to cell) the mouse can be used to move directly to a field or cell while from the keyboard:
- the TAB key moves to the next field.
- the shift TAB moves to the previous field.
In fields/cells that are combo boxes with drop down lists: -
- In the boxed field format the drop down list appears when the left mouse is clicked
- In the tabular format the mouse must be used to bring up the list.
- In any combo box the list can be traversed using the up and down arrow keys or by direct selection with the mouse.
Editing a Field
In the boxed field format, once the cursor is moved to the field, hitting delete will clear the field. To overwrite the current value, highlight the value and type in a new value. The left and right arrow keys allows the user to move to and edit specific numbers or letters in the field.
In the tabular format once the cursor is moved to a particular cell clicking the left mouse will invoke edit mode with the value in the cell highlighted. Editing is then as for the box field format.
On many of the tables of input, the rows of data can be sorted with sort selection by clicking the required column header.
FAQ (Frequently Asked Questions)
Q. How often do I have to save my data ?
A. The input data for the program is automatically saved in a data base as it is entered. For the calculations however, a text file in a specific format is required. This is achieved by selecting SAVE or SAVE AS and in fact the data must be saved in this way before the calculations are performed. In theory then there is no need to SAVE your data until you wish to do the calculations because even if someone pulls the plug the data will be in your project data-base.
Murphy's 39th law however states that if you are assured nothing will ever go wrong it will go wrong; so on a large job it is a good idea to SAVE your data in a text file every so often as a back up to the data base. If the data base is somehow corrupted, you can then open the saved project and this will load the text file into the data base (.mdb file)
Q. Why can't I see all of the forms on the screen ?
A. The program runs with a minimum 600X800 (SVGA) screen resolution. VGA screens (480x640) can't display the whole form. You also need to have the text size set to small fonts in your WINDOWS Settings.
Q. How do you use the program to analyse systems with more than 1100 sprinklers ?
A. To model large systems with more operating sprinklers than 1100 a section of the system remote from the input point that can be isolated by a single connecting pipe must be analysed first with Calculate “Input Point Flow/Pressure” on. The node at the end of this connecting pipe is the input pipe for this run. This can be repeated for any other groups of pipes that can be isolated.
Once the flow and pressure at these connecting point nodes are determined, then each of these sections of the system are modeled as single sprinklers with a k factor calculated from the flow and pressure listed in the results of the initial runs, and the minimum flow as the flow calculated in these initial runs. By using these k factors, the actual flow and pressure at these points will be determined when the whole system is run.
Finally, the flow at all sprinklers in each section can be determined by re-running the initial runs but this time without FDESPT and with the input pressure as listed in the results for the whole system at each "input" node.