Remote

When the Remote Area is entered on the Operating Sprinklers Tab Page, the program will calculate the hydraulically most remote (unfavourable) region for the nominated operating (discharging) sprinkler heads by moving the operating sprinklers around the GRID over the area specified.

In the results the following is listed for each position as the operating sprinklers are moved around the remote area:

·         The column and row number of the bottom left and top right corner of the rectangle enclosing the operating sprinklers.

·        The flow and  node number of the operating sprinkler with the least flow at this location.

·        The total flow from all the operating sprinklers at this location

·        The node number and pressure at each input point.

If “Calculate Discharge Flows for Given Input” is selected the flow and pressure is calculated at each input point and the one with the highest pressure is listed as the MOST remote. The location with the highest minimum flow is then labelled as the LEAST remote.

If “Calculate Input Point Flow/Pressure” is selected.    First the required Input Point  pressure for each location to meet the minimum discharge requirement is calculated. The location with the highest value is labelled as the MOST remote. This Input pressure is then used for all other locations to determine the highest minimum flow which is then labelled as the LEAST remote.

If “Calculate Pump Flow/Pressure” is selected.    First the required  Booster Pump pressure for each location to meet the minimum discharge requirement is calculated. The location with the highest value is labelled as the MOST remote. This booster pump pressure is then used for all other locations (with the Input pressure based on the entered curve) to determine the highest minimum flow which is then labelled as the LEAST remote.

If “Calculate Input Point or Booster Pump Flow/Pressure” is selected , the discharge flows for the MOST favourable region will normally be higher at this location and to calculate the actual flows a separate run with the sprinkler locations and the selected input point or booster pump curve is required