Other Fittings
If there are any other fittings in the pipe, they are selected on the selection form that appears when the right mouse is clicked . Fittings (including valves) that apply to the Sprinkler Code (as selected on the Project Tab Page and the particular pipe material) are displayed for the current pipe. In addition where appropriate User Defined fittings are also displayed. The user defined fittings are fitting types with the appropriate equivalent lengths entered by the User using the USER DATA Button on the Main Screen.
The number of Standard Elbows/Bends and 90° Branch Tees (as entered in the previous two columns in the Pipes Table) are included in the selection form.
For hydrant mill cocks there is no data available and an angle valve (NV) may be used.
The following items are on the Tool Bar:
Units - The units of Length and Diameter currently in use.
The current pipe diameter
Fitting String - As the user enters the number of fittings and the appropriate data (length or diameter) as required, the string that is written out to the input data file is displayed here, e.g. 2GV ZAV(400) LE(40). The fittings for this particular pipe will also appear this way under other fittings ( except for the number of Standard Elbows and 90° Branch Tees) on the Pipes Tab Page.
  Clears all entered data for this pipe
In the selection fform users can enter data in the various columns for:
Special Fittings - Fittings with a user entered equivalent length.
Fittings with a different diameter
Unlabled Fitting (**) with a user entered equivalent length.
Pressure Control Devices  (Pipes Tab only)
In the selection list the fitting code (e.g. SE) and description are displayed. Symbols are displayed in the description of some of the fittings. These indicate the source of the data for equivalent lengths used for the particular fitting and are:
[M.H.]Â Municipal Hydraulics, Vancouver Canada
[G.B.]Â Gage Babcock, Vancouver Canada
[Crane]Â Crane Company Catalogue No.41
[ASC]Â Automatic Sprinkler Corporation of America
[KA] Katmar Software
[PPI] Plastic Pipe Institute USA
(SE), (TT), (AS2118), (no loss), etc.
The items (in circular brackets) indicate that the particular Code does not have values for this particular fitting and the letters within the brackets, signify the fitting or code which is used in determining the equivalent length. E.g., in NFPA the straight through Tees (TN) and (TR) are taken as the same as a long radius elbow (LE) and a short radius elbow (SE) respectively, whilst in other codes they are assumed to have (no loss). Another example is the values for the Check Alarm Mushroom which are taken from (AS2118).
For HDPE and Stainless Steel Tube fittings, L/D ratios are used but users can enter their own pressure loss data using values of equivalent length as for other pipe materials. The L/D ratios were based on data from Katmar Software and an article by the Plastic Pipe Institute USA â âDesign of PE Piping Systems Chapter 6â. The program does not allow User defined fittings for these pipe materials.
At the foot of the Selection box any errors in the entered fitting data are displayed together with the current erroneous fitting string.
Select here for further information on Fitting Equivalent lengths including tables of actual values.