These are the node numbers assigned by the user to the nodes at either end of the pipe. A node must be entered wherever there is:

  • an operating sprinkler
  • a nozzle on a hose or hose reel
  • a hydrant
  • a fixed discharge
  • an input point
  • a junction of three or more pipes
  • a point where a pipe changes size or material

Note that if there is a check valve in the pipe and check valve action is required the nodes must be in the order that will give flow when the check valve is open. Also if a pipe contains a booster pump or back flow preventer the nodes must be entered in the direction of flow. In all other cases they can be entered in any order,