Node A and Node B
These are the node numbers assigned by the user to the nodes at either end of the pipe. A node must be entered wherever there is:
- an operating sprinkler
- a nozzle on a hose or hose reel
- a hydrant
- a fixed discharge
- an input point
- a junction of three or more pipes
- a point where a pipe changes size or material
Note that if there is a check valve in the pipe and check valve action is required the nodes must be in the order that will give flow when the check valve is open. Also if a pipe contains a booster pump or back flow preventer the nodes must be entered in the direction of flow. In all other cases they can be entered in any order,