Min. Press.

The minimum or residual pressure required at the hydrant/standpipe connection point. This is used with the entered Minimum flow to determine the equivalent k factor. The program then uses this calculated k factor for all the entered hydrants or stand pipes to determine the most remote hydrant/standpipe when Calculate input flow and pressure” is selected on the Project Screen. When “Discharge flows for given input” is selected, the calculated k factor is used to determine the flow based on the pressure at the hydrant/standpipe node.

Hydrants (From AS2419 – 2005)

Type of HydrantMinimum Flow Rate****L/sMin. Residual Pressure****kPa
Feed fire hydrant unassisted  - NSW                                               - Other States1010150200
Attack fire Hydrant, unassisted - NSW                                                   - Other States1010250350
Internal and external fire hydrant when boosted by a fire brigade pumping appliance10 700 
Attack fire hydrant performance achieved without the use of a fire brigade pumping appliance5 700
Hydrant pumped max pressure51200
Hydrant pumped max pressure at valve shut01300

Hose Reels (from AS2441 -  2005)

Nominal Hose DiameterMinimum Flow RateMinimum Required Pressure  (+ 10 kPa)
mmL/sL/minkPa
190.3320220
250.4125220