Fittings to:
This is the Sprinkler Code on which the equivalent lengths of fittings (entered on the Pipes Tab Page) are to be based viz.
NFPA National Fire Protection Association (USA) Installation of Fire Sprinklers
AS2118 Australian Standard 2118 Part 1 Automatic Fire Sprinkler Systems
NZ4541 New Zealand Standard 4541 Automatic Fire Sprinkler Systems
SSCP52 Singapore Standard CP52 - Code of Practice for Automatic Fire Sprinkler Systems
AS4587 Australian Standard 4587 (1999) for Water mist fire protection systems
NFPA750 National Fire Protection Association (USA) for Water mist fire protection systems
GB50084 Chinese Standard Automatic Fire Sprinkler Systems
NFPA750 and AS4587 are for mist systems. In both these codes, equivalent lengths for copper fittings are listed and used by the program. However fitting equivalent lengths, as listed in the User Guide for stainless steel pipe (SS40 and SS10) and any user defined stainless steel tubing are also available.
In North America the program only allows NFPA, NFPA750 and GB50084. In other locations a selection between NFPA, NFPA750, AS2118, AS4587, NZ4541, SSCP52 or GB50084 is available.
For fire hydrant or hose reel installations the fitting equivalent lengths of NFPA may be used. These values agree, within a few percent, with the data published in the Crane Company Catalogue No. 41. For hydrant mill cocks it is suggested that an angle valve (NV) be used.
A default value can be set for new projects under Set Defaults under System Configuration accessed from the Menu Bar on the Main Screen.