Equivalent Lengths (feet) Used by Program for NFPA Commercial (NFPA13 & 13R)
Nominal Diameter of Fitting (in)** **
Fittings** 0.5 0.75 1.0 1.25 1.5 2.0 2.5 3.0 3.5 4.0 5.0 6.0 **Source\ Screwed Fittings based on Schedule 40 steel pipe to ASTM A-153, A-795 (HWCoef 120)\ Stand elbow SE 1* 2 2 3 4 5 6 7 8 10 12 14 2\ 45° turn elbow HE 1* 1 1 1 2 2 3 3 3 4 5 7 2\ Long radius elbow LE 0.5 1 2 2 2 3 4 5 5 6 8 9 2\ Tee 90° turn TT 3 4 5 6 8 10 12 15 17 20 25 30 2\ Tees straight\ through\ -non reducing TN No Loss\ -reduced l/2 TR No Loss\ \ Valves etc based on Schedule 40 steel pipe to ASTM A-153, A-795 (HWCoef 120)\ Gate Valve GV 1* 1* 1 1 1 1 1 1 1 2 2 3 2\ Check Valve CV 5 7 9 11 14 16 19 22 27 32 2\ Globe Valve LV 16 20 25 34 41 53 61 80 90 101 120 160 5\ Angle Valve NV 8 11 13 18 21 27 32 40 47 55 60 82 5\ Butterfly Valve BV 6 7 10 11* 12 9 10 4\ Alarm Valve AV 0.05 0.2 0.4 1.2 3 8 10 12 15 20 4\ Mushroom Valve MV 42.1 70.2 1\ Drypipe Valve DV 0.1 0.2 0.5 1.5 3.5 10 12 18 20 30 4\ Strainer SR 0.1 0.4 0.75 2.5 6.0 17 20 30 35 40 4\ \ Flanged or socket (slip) fittings based on Unlined Cast Iron pipe to ANSI/AWWA(HW 100)\ 90° elbow E1 6 8* 10 3\ 45° elbow E2 3 3.5* 4 3\ Tee T1 11 14* 17 3\ Tee T2 9 11.5* 14 3\ Tee T3 14 18* 22 3\ Tee T4 11 14* 17 3\ Cross C1 12 16* 20 3\ Cross C2 10 13* 16 3\ Cross C3 13 17* 21 3\ Cross C4 11 14* 17 3\ \ Nominal Diameter of Fitting (in) ** \ Fittings **6.0 8.0 9.0 10.0 12.0 14.0 15.0 16.0 18.0 20.0 22.0 24.0 **Source**\ Screwed Fittings based on Schedule 40 steel pipe to ASTM A-153, A-795 (HWCoef 120)\ Stand elbow SE 14 18 20* 22 27 30 31* 32 38 2\ 45° turn elbow HE 7 9 10* 11 13 15 16* 17 20 2\ Long radius elbow LE 9 13 14. 5* 16 18 2\ Tee 90° turn TT 30 35 42.5* 50 60 65 67.5* 70 80 2\ Tees straight through\ -non reducing TN No Loss\ -reduced l/2 TR No Loss\ Valves etc based on Schedule 40 steel pipe to ASTM A-153, A-795 (HW Coef 120)\ Gate Valve GV 3 4 4.5* 5 6 6 6.5* 7 8 2\ Check Valve CV 32 45 50* 55 65 70 72.5* 75 85 2\ Globe Valve LV 160 210 250 290 340 5\ Angle Valve NV 82 105 125 145 170 5\ Butterfly Valve BV 10 12 15.5* 19 21 4\ Alarm Valve AV 20 32 4\ Mushroom Valve MV70.2 105 140 1\ Drypipe Valve DV 30 4\ Strainer SR 40 70 4\ Flanged or socket (slip) fittings based on Unlined Cast Iron pipe to ANSI/AWWA(HW Coef 100)**\ 90° elbow E1 10 13 17 21 25 26.5* 28 32 36 40* 44 3\ 45° elbow E2 4 6 7 9 10 11* 12 14 15 16.5* 18 3\ Tee T1 17 24 30 37 44 47.5* 51 58 65 72.5* 80 3\ Tee T2 14 19 24 30 35 38* 41 47 52 58* 64 3\ Tee T3 22 30 39 48 57 61* 65 75 84 93.5* 103 3\ Tee T4 17 24 30 37 44 47.5 51 58 65 72.5* 80 3\ Cross C1 20 28 36 44 53 57.5* 62 70 79 88.5* 98 3\ Cross C2 16 22 28 34 41 44.5* 48 54 61 68.5* 76 3\ Cross C3 21 29 38 47 56 60.5* 65 74 83 93* 103 3\ Cross C4 17 24 31 39 46 50* 54 61 69 77* 85 3\ \ Legend for Source:**
1 = AS 2118
2 = NFPA up to 12 inch and reference 3 beyond 12 inch
3 = Data from Automatic Sprinkler Corporation of America.
4 = Data included by Municipal Hydraulics
5 = Crane Co. Catalogue No. 41
- indicates interpolated values