Calculate Input Point Flow/Pressure

If the user wishes to calculate the required flow and pressure at the input point to the system such that the water flow at each discharging nozzle or sprinkler is not less than the minimum specified quantity, Calculate Input Flow/Pressure is selected. The entered discharge at each  sprinkler, nozzle and hydrant is then the minimum design quantity and the entered pressure at the input point (either as a constant pressure or a characteristic curve) is only used in evaluating the first estimate of the flow throughout the network.